Industrial Protocols |
| CAN Port |
1 |
| CAN Version |
CANopen |
Analog Input |
| Total channels of analog input |
10 |
| Differential channels |
10 |
| Voltage range |
+/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, +/-10 V |
| Current range |
-20...+20 mA |
| Current mode |
Requires optional external 125 ohm resistor |
| Thermocouple |
K: -270...+1372 °С, T: -270...+400 °С, E: -270...+1000 °С, B: 0...1820 °С, N: -270...+1300 °С, C: 0...+2320 °С, J: -210 ... +1200°C, R: -50 ... +1765°C, S: -50 ... +1765°C |
| Sampling rate |
10 Hz |
| Resolutions |
16 Bit |
| Accuracy |
0.1 % |
Connectors / Cables |
| Connectors |
DB25 |
Watchdog |
| Hardware |
Yes |
System Power Input |
| Input Voltage DC |
10~30 V |
| Power Consumption |
1.5 W |
| Power Input Isolation |
3000 V |
Operating Conditions |
| Temperature |
-25~75 °C |
| Humidity |
10~90 % |
Storage Conditions |
| Temperature Range |
-30~80 °C |
Construction |
| Construction Chassis |
Plastic Chassis |
| Mounting Configuration |
DIN-Rail mount |
Dimensions and weight |
| Width |
33 mm |
| Height |
78 mm |
| Depth |
99 mm |