Interfaces |
| RS-485 |
1 |
| Maximum Transfer Rate RS-485 |
921600 Bit/s |
Industrial Protocols |
| Modbus RTU |
Slave |
Digital Input |
| Total channels of digital input |
8 |
| Type |
Dry contact, Wet contact |
| On voltage level for wet contact |
10~30 V |
| Off voltage level for wet contact |
0~3 V |
| On voltage level for dry contact |
Connected to GND |
| Off voltage level for dry contact |
Open |
| Counter |
2.5KHz, 16 bit |
| Isolation of Digital Input |
3000 V |
Digital Output |
| Total channels of digital output |
8 |
| Sink/Source |
Sink |
| Max. load current |
200 mA |
System Power Input |
| Input Voltage DC |
12~48 V |
Operating Conditions |
| Temperature |
-10~75 °C |
| Humidity |
5~95 % |
Storage Conditions |
| Temperature Range |
-40~85 °C |
| Humidity |
5~95 % |
Construction |
| Construction Chassis |
Plastic Chassis |
| Mounting Configuration |
DIN-Rail mount |
Dimensions and weight |
| Width |
27.8 mm |
| Height |
124 mm |
| Depth |
84 mm |
Standards and Certifications |
| Vibration And Shock |
IEC 60068-2-6, IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Safety |
UL 508 |
| EMS |
EN 55024, IEC 61000-4, IEC 61000-6, EN 61000-4-2, EN 61000-4-5 |
| EMI |
EN 55022, FCC Part 15, EN 61000-3-2, EN 61000-3-3 |