Interfaces |
RS-485 |
1 |
Maximum Transfer Rate RS-485 |
115200 Bit/s |
Industrial Protocols |
Modbus RTU |
Slave |
DCON |
Slave |
Analog Input |
Total channels of analog input |
4 |
Differential channels |
4 |
Voltage range |
+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V |
Current range |
0...20 mA, 4...20 mA, -20...+20 mA |
Current mode |
Jumper Selectable |
Sampling rate |
10 Hz |
Resolutions |
16 Bit |
Accuracy |
0.1 % |
Digital Input |
Total channels of digital input |
5 |
Type |
Wet contact |
Sink/Source |
Sink, Source |
On voltage level for wet contact |
10~50 V |
Off voltage level for wet contact |
0~4 V |
Counter |
50Hz, 16 bit |
Digital Output |
Total channels of digital output |
4 |
Type |
Electromagnitic relay |
Relay (Form A) |
4 |
Contact rating of relay (Form A) |
5A@250V AC, 5A@30V DC |
Operate time |
6 ms |
Watchdog |
Hardware |
Yes |
Programmable |
Yes |
System Power Input |
Input Voltage DC |
10~30 V |
Power Consumption |
1.8 W |
Operating Conditions |
Temperature |
-25~75 °C |
Humidity |
10~95 % |
Storage Conditions |
Temperature Range |
-40~80 °C |
Construction |
Construction Chassis |
Plastic Chassis |
Mounting Configuration |
Wall, DIN-Rail mount |
Dimensions and weight |
Width |
72 mm |
Height |
123 mm |
Depth |
35 mm |
Standards and Certifications |
EMS |
IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5 |