Interfaces |
| RS-485 |
1 |
| Maximum Transfer Rate RS-485 |
115200 Bit/s |
Industrial Protocols |
| Modbus RTU |
Slave |
| DCON |
Slave |
Analog Input |
| Total channels of analog input |
6 |
| Differential channels |
6 |
| Voltage range |
+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V |
| Current range |
0...20 mA, 4...20 mA, -20...+20 mA |
| Current mode |
Jumper Selectable |
| Sampling rate |
10 Hz |
| Resolutions |
16 Bit |
| Accuracy |
0.1 % |
| Isolation of Analog Input |
400 V |
Analog Output |
| Channels of analog output |
2 |
| Voltage range |
0...5 V, 0...10 V, +/-5 V, +/-10 V |
| Current range |
0...20 mA, 4...20 mA |
| Resolution |
12 Bit |
| Accuracy |
0.01 % |
Digital Input |
| Total channels of digital input |
3 |
| Type |
Dry contact |
| Sink/Source |
Source |
| On voltage level for dry contact |
Connected to GND |
| Off voltage level for dry contact |
Open |
| Counter |
100Hz, 16 bit |
Digital Output |
| Total channels of digital output |
3 |
| Type |
Open collector |
| Sink/Source |
Sink |
| Load voltage |
3.5~50 V |
| Max. load current |
700 mA |
Watchdog |
| Hardware |
Yes |
| Programmable |
Yes |
System Power Input |
| Input Voltage DC |
10~30 V |
| Power Consumption |
1.8 W |
Operating Conditions |
| Temperature |
-25~75 °C |
| Humidity |
10~95 % |
Storage Conditions |
| Temperature Range |
-40~80 °C |
Construction |
| Construction Chassis |
Plastic Chassis |
| Mounting Configuration |
Wall, DIN-Rail mount |
Dimensions and weight |
| Width |
72 mm |
| Height |
123 mm |
| Depth |
35 mm |
Standards and Certifications |
| EMS |
IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5 |