Skip to content

M-7026

by ICP DAS
Price on request
6-channel Analog Input, 2-channel Analog Output, 3-channel Digital Input and 3-channel Digital Output Module using the DCON and Modbus Protocol (Gray Cover) (RoHS)

Interfaces

RS-485 1
Maximum Transfer Rate RS-485 115200 Bit/s

Industrial Protocols

Modbus RTU Slave
DCON Slave

Analog Input

Total channels of analog input 6
Differential channels 6
Voltage range +/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V
Current range 0...20 mA, 4...20 mA, -20...+20 mA
Current mode Jumper Selectable
Sampling rate 10 Hz
Resolutions 16 Bit
Accuracy 0.1 %
Isolation of Analog Input 400 V

Analog Output

Channels of analog output 2
Voltage range 0...5 V, 0...10 V, +/-5 V, +/-10 V
Current range 0...20 mA, 4...20 mA
Resolution 12 Bit
Accuracy 0.01 %

Digital Input

Total channels of digital input 3
Type Dry contact
Sink/Source Source
On voltage level for dry contact Connected to GND
Off voltage level for dry contact Open
Counter 100Hz, 16 bit

Digital Output

Total channels of digital output 3
Type Open collector
Sink/Source Sink
Load voltage 3.5~50 V
Max. load current 700 mA

Watchdog

Hardware Yes
Programmable Yes

System Power Input

Input Voltage DC 10~30 V
Power Consumption 1.8 W

Operating Conditions

Temperature -25~75 °C
Humidity 10~95 %

Storage Conditions

Temperature Range -40~80 °C

Construction

Construction Chassis Plastic Chassis
Mounting Configuration Wall, DIN-Rail mount

Dimensions and weight

Width 72 mm
Height 123 mm
Depth 35 mm

Standards and Certifications

EMS IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5