Construction |
| Construction Chassis |
Plastic Chassis |
| Mounting Configuration |
DIN-Rail mount |
Network Adapter |
| Total Ethernet |
1 |
| 10/100 Mbit/s |
1 |
Industrial Protocols |
| Modbus TCP |
Slave |
AC Power Measurement |
| CT Type |
Split-core CT |
| Wiring |
3P4W-3CT, 3P3W-3CT, 3P3W-2CT, 1P2W-1CT, 1P3W-2CT |
| Input Voltage |
10...500V AC |
| Input Current |
200А |
| Frequency |
50/60Hz |
| Power Parameter Measurement |
True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Current measurement channels |
24 |
| Voltage measurement channels |
1 (three-phase) |
Digital Output |
| Total channels of digital output |
2 |
| Type |
Electromagnitic relay |
| Relay (Form A) |
2 |
| Contact rating of relay (Form A) |
5A@250V AC, 5A@30V DC |
Connectors / Cables |
| Connectors |
Screw Terminal |
System Power Input |
| Input Voltage AC |
85~264 V |
| Power Consumption |
6 W |
Operating Conditions |
| Temperature |
-20~70 °C |
| Humidity |
10~90 % |
Storage Conditions |
| Temperature Range |
-25~80 °C |
Dimensions and weight |
| Width |
52 mm |
| Height |
134 mm |
| Depth |
237 mm |