Məhsul tələbi
Interfaces |
|
| RS-485 | 1 |
| Maximum Transfer Rate RS-485 | 115200 Bit/s |
Industrial Protocols |
|
| Modbus RTU | Slave |
| DCON | Slave |
Digital Input |
|
| Total channels of digital input | 14 |
| Type | Wet contact |
| Sink/Source | Sink, Source |
| On voltage level for wet contact | 0~1 V |
| Off voltage level for wet contact | 4~30 V |
| Counter | 100Hz, 16 bit |
Connectors / Cables |
|
| Connectors | Screw Terminal |
Watchdog |
|
| Hardware | Yes |
| Programmable | Yes |
System Power Input |
|
| Input Voltage DC | 10~30 V |
| Power Consumption | 0.2 W |
Operating Conditions |
|
| Temperature | -25~75 °C |
| Humidity | 5~95 % |
Storage Conditions |
|
| Temperature Range | -40~85 °C |
Construction |
|
| Construction Chassis | Plastic Chassis |
| Mounting Configuration | Wall, DIN-Rail mount |
Dimensions and weight |
|
| Width | 72 mm |
| Height | 123 mm |
| Depth | 35 mm |
Standards and Certifications |
|
| EMS | IEC 61000-4-2, IEC 61000-4-4 |