Məhsul tələbi
Interfaces |
|
RS-485 | 1 |
Maximum Transfer Rate RS-485 | 115200 Bit/s |
Industrial Protocols |
|
Modbus RTU | Slave |
Modbus ASCII | Slave |
DCON | Slave |
Digital Input |
|
Total channels of digital input | 4 |
Type | Wet contact |
Sink/Source | Sink |
On voltage level for wet contact | 3.5~50 V |
Off voltage level for wet contact | 0~1 V |
Counter | 100Hz, 16 bit |
Digital Output |
|
Total channels of digital output | 4 |
Type | Open emmiter |
Sink/Source | Source |
Load voltage | 10~40 V |
Max. load current | 700 mA |
Connectors / Cables |
|
Connectors | Screw Terminal |
Watchdog |
|
Hardware | Yes |
Programmable | Yes |
System Power Input |
|
Input Voltage DC | 10~30 V |
Power Consumption | 0.5 W |
Operating Conditions |
|
Temperature | -25~75 °C |
Humidity | 5~95 % |
Storage Conditions |
|
Temperature Range | -35~75 °C |
Construction |
|
Construction Chassis | Plastic Chassis |
Mounting Configuration | DIN-Rail mount |
Dimensions and weight |
|
Width | 52 mm |
Height | 98 mm |
Depth | 27 mm |
Standards and Certifications |
|
EMS | IEC 61000-4-2, IEC 61000-4-4 |