перейти к содержанию

PFN-2019/S

Цена по запросу
PROFINET I/O Module (10-ch AI) (RoHS)

Network Adapter

10/100 Mbit/s 2
Type 10/100 Mbit/s RJ-45

Industrial Protocols

PROFINET I/O Slave

Analog Input

Total channels of analog input 10
Differential channels 10
Voltage range +/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, +/-10 V
Current range 0...20 mA, 4...20 mA, -20...+20 mA
Current mode Jumper Selectable
Thermocouple J: -210...+760 °С, K: -270...+1372 °С, T: -270...+400 °С, E: -270...+1000 °С, R: 0...1768 °С, S: 0...1768 °С, B: 0...1820 °С, N: -270...+1300 °С, C: 0...+2320 °С
Sampling rate 10 Hz
Resolutions 16 Bit
Accuracy 0.1 %

Connectors / Cables

Connectors Screw Terminal

System Power Input

Input Voltage DC 10~30 V
Power Consumption 5 W

Operating Conditions

Temperature -25~75 °C
Humidity 10~90 %

Storage Conditions

Temperature Range -30~80 °C

Construction

Construction Chassis Plastic Chassis
Mounting Configuration DIN-Rail mount

Dimensions and weight

Width 33 mm
Height 126 mm
Depth 93 mm