перейти к содержанию

tM-DA1P1R1

Цена по запросу
1-channel Isolated Analog Output, 1-channel Isolated Digital Input and 1-channel Relay Output Module (RoHS)

Interfaces

RS-485 1
Maximum Transfer Rate RS-485 115200 Bit/s

Industrial Protocols

Modbus RTU Slave
Modbus ASCII Slave
DCON Slave

Analog Output

Channels of analog output 1
Voltage range 0...10 V
Current range 0...20 mA, 4...20 mA
Resolution 12 Bit
Accuracy 0.1 %

Digital Input

Total channels of digital input 1
Type Dry contact
Sink/Source Dry: Source
On voltage level for dry contact Connected to GND
Off voltage level for dry contact Open
Counter 100Hz, 16 bit

Digital Output

Total channels of digital output 1
Type Electromagnitic relay
Relay (Form C) 1
Contact rating of relay (Form C) 10A(NO)/6A(NC)@250V AC

Connectors / Cables

Connectors Screw Terminal

Watchdog

Hardware Yes
Programmable Yes

System Power Input

Input Voltage DC 10~30 V

Operating Conditions

Temperature -25~75 °C
Humidity 10~90 %

Storage Conditions

Temperature Range -30~80 °C

Construction

Construction Chassis Plastic Chassis
Mounting Configuration DIN-Rail mount

Dimensions and weight

Width 52 mm
Height 98 mm
Depth 27 mm

Standards and Certifications

EMS IEC 61000-4-2, IEC 61000-4-4